• Motor current setting (thermal) is not specifi ed by NEC/CEC
• MCP breakers are magnetic only
• Thermal capability should be greater than or equal to motor FLA and less than or equal to overload relay setting
• Motor Overload protection must be provided separately
• MCPs are UL Recognized
• Must be tested and listed with specifi c contactors and overloads
• UL Listing is obtained as part of UL 508 Type D combination starters
• Magnetic Trip Current is adjustable
• Adjustability is required by UL489 standard
• Must be sized per NEC/CEC rules – ≤ 800% motor FLA for standard effi ciency motors – ≤ 1300% motor FLA allowed if motor will not start – ≤ 1100% motor FLA for high effi ciency motors – ≤ 1700% motor FLA allowed if motor will not start
• MCPs are the most popular choice for motor circuits in the North American market
• Used in combination starters and MCC buckets for many years
• Provide choice in overload protection